New single-ended earthfault distance estimation for the 110-kV- and 20-kV-compensated network

Gernot Druml, Georg Achleitner, Wolfgang Leitner, Lothar Fickert

Research output: Contribution to journalArticleResearchpeer-review

Abstract

Due to today´s increased demands on grid operation management, new methods for earth fault localization and detection are needed. The fault localization should be performed as quickly as possible and under the condition, that the fault current at the fault location will not be significantly increased. The pros and cons of Distance Protection in solid grounded networks are well known. In case of a single-line earthfault, the current via the fault location in solid grounded networks is in the range of some kA. In compensated networks the residual current Ires via the fault location is, in case of a single line fault, only few ampere. Very often this current is much smaller than the load current of the feeder. A distinction between load current, circulating currents in meshed networks and fault current is more or less not possible. Therefore, the Earthfault-Distance-Protection in compensated networks is usually switched off. With the new transient relays, based on the qu2-algorithm, it is possible to detect in the substation very reliable the faulty feeder and the direction of the fault. This statement is also correct for meshed networks. In a 110-kV-network the distance between two substations is in the range of 50 km to 200 km. Also if the feeder is identified correctly, it is still a challenge to locate the exact fault position on this feeder. The results of field-test in a 110-kV-network with different fault impedances will be presented.

Original languageEnglish
Pages (from-to)567-575
Number of pages9
Journale&i - Elektrotechnik und Informationstechnik
Volume135
Issue number8
DOIs
Publication statusPublished - 1 Dec 2018

Fingerprint

Electric fault location
Electric fault currents
Earth (planet)

Keywords

  • Fault location
  • Simulation tool
  • Two-end data algorithm

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Cite this

New single-ended earthfault distance estimation for the 110-kV- and 20-kV-compensated network. / Druml, Gernot; Achleitner, Georg; Leitner, Wolfgang; Fickert, Lothar.

In: e&i - Elektrotechnik und Informationstechnik, Vol. 135, No. 8, 01.12.2018, p. 567-575.

Research output: Contribution to journalArticleResearchpeer-review

@article{3651841ad02a4d53bb5cf3adb38a7250,
title = "New single-ended earthfault distance estimation for the 110-kV- and 20-kV-compensated network",
abstract = "Due to today´s increased demands on grid operation management, new methods for earth fault localization and detection are needed. The fault localization should be performed as quickly as possible and under the condition, that the fault current at the fault location will not be significantly increased. The pros and cons of Distance Protection in solid grounded networks are well known. In case of a single-line earthfault, the current via the fault location in solid grounded networks is in the range of some kA. In compensated networks the residual current Ires via the fault location is, in case of a single line fault, only few ampere. Very often this current is much smaller than the load current of the feeder. A distinction between load current, circulating currents in meshed networks and fault current is more or less not possible. Therefore, the Earthfault-Distance-Protection in compensated networks is usually switched off. With the new transient relays, based on the qu2-algorithm, it is possible to detect in the substation very reliable the faulty feeder and the direction of the fault. This statement is also correct for meshed networks. In a 110-kV-network the distance between two substations is in the range of 50 km to 200 km. Also if the feeder is identified correctly, it is still a challenge to locate the exact fault position on this feeder. The results of field-test in a 110-kV-network with different fault impedances will be presented.",
keywords = "Fault location, Simulation tool, Two-end data algorithm",
author = "Gernot Druml and Georg Achleitner and Wolfgang Leitner and Lothar Fickert",
year = "2018",
month = "12",
day = "1",
doi = "10.1007/s00502-018-0663-y",
language = "English",
volume = "135",
pages = "567--575",
journal = "e&i - Elektrotechnik und Informationstechnik",
issn = "0932-383X",
publisher = "Springer Wien",
number = "8",

}

TY - JOUR

T1 - New single-ended earthfault distance estimation for the 110-kV- and 20-kV-compensated network

AU - Druml, Gernot

AU - Achleitner, Georg

AU - Leitner, Wolfgang

AU - Fickert, Lothar

PY - 2018/12/1

Y1 - 2018/12/1

N2 - Due to today´s increased demands on grid operation management, new methods for earth fault localization and detection are needed. The fault localization should be performed as quickly as possible and under the condition, that the fault current at the fault location will not be significantly increased. The pros and cons of Distance Protection in solid grounded networks are well known. In case of a single-line earthfault, the current via the fault location in solid grounded networks is in the range of some kA. In compensated networks the residual current Ires via the fault location is, in case of a single line fault, only few ampere. Very often this current is much smaller than the load current of the feeder. A distinction between load current, circulating currents in meshed networks and fault current is more or less not possible. Therefore, the Earthfault-Distance-Protection in compensated networks is usually switched off. With the new transient relays, based on the qu2-algorithm, it is possible to detect in the substation very reliable the faulty feeder and the direction of the fault. This statement is also correct for meshed networks. In a 110-kV-network the distance between two substations is in the range of 50 km to 200 km. Also if the feeder is identified correctly, it is still a challenge to locate the exact fault position on this feeder. The results of field-test in a 110-kV-network with different fault impedances will be presented.

AB - Due to today´s increased demands on grid operation management, new methods for earth fault localization and detection are needed. The fault localization should be performed as quickly as possible and under the condition, that the fault current at the fault location will not be significantly increased. The pros and cons of Distance Protection in solid grounded networks are well known. In case of a single-line earthfault, the current via the fault location in solid grounded networks is in the range of some kA. In compensated networks the residual current Ires via the fault location is, in case of a single line fault, only few ampere. Very often this current is much smaller than the load current of the feeder. A distinction between load current, circulating currents in meshed networks and fault current is more or less not possible. Therefore, the Earthfault-Distance-Protection in compensated networks is usually switched off. With the new transient relays, based on the qu2-algorithm, it is possible to detect in the substation very reliable the faulty feeder and the direction of the fault. This statement is also correct for meshed networks. In a 110-kV-network the distance between two substations is in the range of 50 km to 200 km. Also if the feeder is identified correctly, it is still a challenge to locate the exact fault position on this feeder. The results of field-test in a 110-kV-network with different fault impedances will be presented.

KW - Fault location

KW - Simulation tool

KW - Two-end data algorithm

UR - http://www.scopus.com/inward/record.url?scp=85057580405&partnerID=8YFLogxK

U2 - 10.1007/s00502-018-0663-y

DO - 10.1007/s00502-018-0663-y

M3 - Article

VL - 135

SP - 567

EP - 575

JO - e&i - Elektrotechnik und Informationstechnik

JF - e&i - Elektrotechnik und Informationstechnik

SN - 0932-383X

IS - 8

ER -