Abstract
The performance of two harmonic emissions assessment methods was tested on field measurements – the harmonic current vector method and the multiplication of harmonic
current magnitudes with network harmonic impedance. With the comparison of obtained emissions with expected steel production plant’s harmonic pollution profile and
characteristic harmonic voltage levels in distribution power network the validity of both methods has been confirmed. The method’s sensibility on harmonic phasors angle inaccuracy and other input parameters has also been examined.
current magnitudes with network harmonic impedance. With the comparison of obtained emissions with expected steel production plant’s harmonic pollution profile and
characteristic harmonic voltage levels in distribution power network the validity of both methods has been confirmed. The method’s sensibility on harmonic phasors angle inaccuracy and other input parameters has also been examined.
Originalsprache | englisch |
---|---|
Titel | 2011 International Conference and Exhibition on Electricity Distribution |
Herausgeber (Verlag) | . |
Publikationsstatus | Veröffentlicht - 2011 |
Veranstaltung | International Conference and Exhibition on Electricity Distribution - Frankfurt Dauer: 6 Juni 2011 → 9 Juni 2011 |